2022 Fulton VSRT-50 50 HP 150 PSI Vertical Spiral Rib Tubeless Steam Boiler with Feedwater Tank

2022 Fulton VSRT-50 50 HP 150 PSI Vertical Spiral Rib Tubeless Steam Boiler with Feedwater Tank

Contact us for price

Location:Miami, FL

Description

OVERVIEW

2022 Fulton VSRT-50 Vertical Spiral Rib Tubeless steam boiler, 50 HP, 150 PSI MAWP, natural gas fired, with a Fulton feedwater tank. Nameplate rating is 1,674,000 BTU/hr output and 1,993,000 BTU/hr input at 0–1,999 ft. Fulton rates the VSRT-50 at 1,725 lb/hr steam from and at 212°F. The boiler is currently installed in a boiler room in Miami, FL, so removal and rigging will be needed. Photos show a Fulton VSRT control panel, a forced-draft burner with blower motor, a cyclonic air inlet silencer, and a separate Fulton feedwater tank skid with its own control panel, pumps, and disconnect. Tank size is not marked on the photos. Built by Fulton Thermal Corporation / Fulton Steam Solutions, Inc., Pulaski, NY.

EQUIPMENT SPECIFICATIONS

  • Manufacturer: Fulton Thermal Corporation / Fulton Steam Solutions, Inc. (Pulaski, NY)
  • Product line: Vertical Spiral Rib Tubeless (VSRT) steam boiler
  • Model: VSRT-50
  • National Board No.: 10689
  • CRN: N/A
  • Year built: 2022 (Manufacturer's Data Report; year is blank on the nameplate)
  • Type: steam, vertical spiral rib tubeless, ASME Section I
  • Fuel: natural gas
  • Shell thickness: .394 in
  • Head thickness: .394 in
  • Heating surface: 116 sq ft (Manufacturer's Data Report; also Fulton VSRT-50 data)
  • MAWP: 150 PSI (Manufacturer's Data Report; not stamped on the nameplate)
  • Shop hydrostatic test: 225 PSI (Manufacturer's Data Report)
  • Mounting: skid (Manufacturer's Data Report)
  • Location: Miami, FL
  • Dimensions (Fulton VSRT-50 2023 brochure, standard configuration): about 97 in high without trim, 107 in with trim, 130 in with burner pull; 49 in wide without trim, 68 in with trim; 83 in deep
  • Weights (Fulton VSRT-50 technical data sheet, standard configuration): 6,000 lb dry, 8,777 lb operating, 9,513 lb flooded; 333 gal water volume at normal working level
  • Connections (Fulton VSRT-50 technical data sheet / data report): 4 in steam outlet, 1 in feedwater, 1-1/2 in bottom blowdown, 3/4 in surface blowdown, 3/4 in high-water protection, 1-1/2 in gas train inlet, 6 in combustion air inlet, 10 in stack; 150 PSI trim safety valve 1 in x 1-1/4 in

Performance Ratings

  • Boiler horsepower: 50 BHP (Fulton VSRT-50 data sheet; matches the nameplate output)
  • Rated steam output: 1,725 lb/hr from and at 212°F (Fulton VSRT-50 data sheet)
  • Maximum designed steaming capacity: 2,070 lb/hr (Manufacturer's Data Report)
  • BTU output: 1,674,000 BTU/hr (nameplate)
  • Max BTU input (0 to 1,999 ft): 1,993,000 BTU/hr (nameplate)
  • Max BTU input (2,000 ft and above): blank on nameplate
  • Minimum input at low fire (Fulton data sheet): 249,000 BTU/hr, 8:1 turndown
  • Natural gas usage at rated input (Fulton data sheet): about 1,993 SCFH
  • Efficiency, emissions: Fulton lists operating efficiencies up to 86% and low NOx below 20 ppm for the VSRT series.

Burner System

  • Forced-draft natural gas burner with blower motor and cyclonic air inlet silencer; Fulton lists a fully modulating 8:1 turndown burner for the VSRT-50
  • Gas supply pressure: 3.0 in WC min, 13.8 in WC max
  • Manifold gas pressure: -2.4 in WC min, -5.56 in WC max
  • Boiler electrical: 460 V / 60 Hz / 3 PH, 17 FLA
  • Controls rating: blank on nameplate
  • Water pump motor rating: blank on the boiler nameplate (the feedwater tank skid has its own panel and pumps)

ADDITIONAL INFORMATION

  • Condition: used, currently installed; removal and rigging required
  • Included equipment: Fulton feedwater tank skid with its own Fulton control panel, pumps, and disconnect, as shown in the photos. Tank capacity is not marked.
  • Manufacturer's Data Report notes: 150 PSI MAWP, 116 sq ft heating surface, 2,070 lb/hr maximum designed steaming capacity, pressure relief valve 1 in x 1-1/4 in set at 150 PSI with 2,585 lb/hr relieving capacity. The Form P-2 header reads "VSRT-60 150#." The nameplate is stamped VSRT-50, and the stamped input and output match Fulton's published VSRT-50 ratings. Fulton's current literature shows the VSRT-50 and VSRT-60 sharing the same vessel size and 116 sq ft heating surface. This listing follows the nameplate as a 50 HP VSRT-50.

Specifications marked as coming from Fulton literature are for standard VSRT-50 configurations and may differ slightly on this 2022 build.

Yard tag: BSF50HP3002

Specifications

ManufacturerFulton
ModelVSRT-50
Year2022
ConditionUsed
Stock NumberBSF50HP3002